Install a ControlNet Coax Media System Chapter 3

Plan the Taps Installation

Follow these guidelines when selecting where to mount the taps based on your

topology

design. Protection of the tap should always be considered when

selecting a location to mount the tap.

If minimum spacing between taps is desired, use a 1786-BNCP barrel to
connect the taps together.

Consider trunk routing, cable bend radius, and device location when
locating and mounting the tap. The bend radius is 1.5 in. for all fixed-tap
drop cables and 3 in. for drop cables pulled through conduit.

Be sure the location where you are going to mount a tap does not cause
any cable bend radii to exceed the limits listed on

page 44

.

Do not mount a tap in a position that routes the drop cable over any
AC power terminals on nearby modules.

Mounting the Taps

You can mount your ControlNet taps (Y-tap and T-tap) in several ways.

Use a universal mounting bracket, and then mount the tap and bracket
as an assembly.

Use the body holes in the tap to mount with screws and flat washers or
a tie wrap.

ATTENTION

Do not allow any metal portions of the tap, connectors, or
cable shields to contact any conductive surfaces. This
contact could cause noise on the ControlNet network.

TIP

See

Appendix A

for universal mounting bracket and tap

mounting dimensions.