Plan a ControlNet Coax Media System Chapter 2

Install Repeaters in Parallel

When you install repeaters in parallel you create smaller, isolated segments that
have less signal noise than larger segments. You can install a maximum of 48
repeaters - the maximum number of taps per 250 m (820 ft) segment - on any
one segment. If your link is configured using repeaters in parallel, you count
one of the repeater taps for one segment and the other repeater tap for the
parallel segment that the repeater is connecting to the backbone network.

The illustration shows an example of repeaters used in parallel.

IMPORTANT

Under no circumstances can delay exceed 121 µs each way in a
network. For more information, see

page 30

.