Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual
Page 12
![background image](/manuals/581124/12/background.png)
10
Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
As a flow totalizer this can be very accurate. However, using it to
calculate flow rate is not as accurate as using analog input I:1.1 as a
flow rate input.
– Press Enter Gallons Per Pulse to set the appropriate gallons per
input pulse
5. Press Next to proceed to the next Digital Inputs Assign screen.
From the remaining Digital Inputs Assign screens you can:
– Press Normally Open or Normally Closed to set the state to
match the way the digital input is wired on the field device.
– Use the Up/Down and End/Home buttons to scroll through the
list of selections
– Digital inputs I:0/0 – I:0/17 are assignable to any of the 31
selections listed; however, depending on the application, they may
not all be applicable. For example, if you only have two pumps in
your system, selection #20 Pump 3 seal fail would not apply