34
Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
7. PowerFlex 4/40 - A106 (comm loss time) = 10 sec., PowerFlex 400 -
C106 (comm loss time) = 10 sec.
The default time of 5 sec. may work satisfactorily, however during
parameter saving and loading, the message instructions in the PLC may
take longer than usual, and the additional time may alleviate some
nuisance communication faults.
8. PowerFlex 4/40 - A107 (comm format) = 0 (RTU 8-N-1), PowerFlex
400 – C102 (comm format) = 0 (RTU 8-N-1)
Panel View C600 (2711C-T6T), Firmware version 1.60
1. IP address: 192.168.1.3
2. Subnet: 255.255.255.0
3. Gateway: 0.0.0.0 (not used)
4. DHCP: Off (not used)
PLC Micro 1400 series A (1766-L32BXB)
1. Analog I/O module 1762-IF2OF2, 2 chnl. Input, 2 chnl. Output