Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual

Page 19

Advertising
background image

Publication IASIMP-QS037A-EN-P - May 2013

17

Chapter 1

3. Pumping sequence example #3: Pump #2 is set for “Lead”, pump

#1 is set for “Lag 1” and pump #3 is set for “Lag2”. When the level
requires a pump to run, pump #2 comes on and runs until the level is
satisfied. If the level continues to change and requires another pump
to run, pump #1 will start. If the level still continues to change and
requires another pump, pump #3 will start. The pumps will continue
to run until the stop level is satisfied. With all pumps now off, when
the level requires a pump to come on, the sequence repeats itself,
there is no alternation.

4. Access other setup screens as needed from the navigation at the bottom

of the Process Config screen.

Press Pump Interlocks to open the Pump Interlocks screen. Refer

to Pump Interlocks on page 17.

Press Backup Pump Selection to open the Backup Pump Selection

screen. Visible only if Float is selected as backup on the Measuring
Setup
screen. Refer to page 12.

Press Pressure Setpoints to open the Pressure Setpoints screen

Visible only if Pressure follower mode is selected. Refer to Pressure
Setpoints on page 19.

Press Level Setpoints to open the Level Setpoints screen. Visible

only if an analog device is being used for measuring level. Refer
to Level Setpoints on page 18.

Pump Interlocks

You can use the Pump Interlocks screen to select from a list of faults that will
inhibit the pump from running.

1. Select and perform the following steps for each pump individually.

Advertising