Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual

Page 34

Advertising
background image

32

Publication IASIMP-QS037A-EN-P - May 2013

Chapter 1

Alarm Output Configuration

From the Alarm Output Configuration screen you can:

Press UP/DOWN to select a process-specific alarm from the list
Press Add Alarm or Remove Alarm to enable or disable the

selected process-specific alarm
The alarms, when enabled, combine to turn on PLC output O:0/9. If
the alarm is not enabled, even though it becomes active, it will not
turn the PLC output on.

Press MORE to add pump-specific alarms from the Pump # Alarm

Output Configuration screen(s). Refer to Pump #1 Alarm Output
Configuration on page 32.

Pump #1 Alarm Output Configuration

Refer to Alarm Output Configuration on page 32 for screen descriptions and
functions. Add and/or remove alarms for the selected pump. Press MORE to