Press Next to proceed to the Backup Pump Select screen.

TIP

The Backup Pump Selection screen is visible only if Float is selected as the
backup on the Measuring Setup screen.

Press the Delay Between Pump Starts (Seconds) to enter the delay
before the next one starts when more than one backup pump is enabled.

TIP

If on the “Measuring Setup” screen (above) the “Secondary (backup) Measuring
Device” is set to “NOT USED”, then no pumps will run in backup.

TIP

If on the “Measuring Setup” screen (above) the “Secondary (backup) Measuring
Device” is set to “Floats”, then backup pumps will start when the “Lead Start”
float is activated, and continue until the “Pumps Stop” float is activated.

A “lead start” and a “pumps stop” selection must be assigned to an input on
one of the “Digital Input Assign” screens.

If during the measuring

buttons will enable or

device setup, floats are
selected as secondary
(backup) then these

disable the pumps from
running in backup mode.