Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual
Page 29

Publication IASIMP-QS037A-EN-P - May 2013
27
Chapter 1
Warning Screen
From the Warning screen you can:
– View the current warning message.
– Press Push to Acknowledge Warning to scroll through each active
warning if multiple warnings exist.
TIP
Although some of the warnings can be alarms, they are typically settings or setup
issues that have conflicts.
List of available warnings:
-- NO WARNINGS EXIST ---
--- PRIMARY MEASURING IS SET FOR
FLOATS ---
--- AND THE MODE IS SET FOR "EMPTY
(PUMP DOWN)" ---
A PUMP IS ASSIGNED TO "LAG2"
AN INPUT NEEDS TO BE ASSIGNED TO
"HIGH LEVEL" OR
THE PUMP NEEDS TO BE IN "OFF"
--- PRIMARY MEASURING IS SET FOR
FLOATS ---
AN INPUT NEEDS TO BE ASSIGNED TO
"PUMPS STOP" AND
AN INPUT NEEDS TO BE ASSIGNED TO
"LEAD START
--- PRIMARY MEASURING IS SET FOR
FLOATS ---
--- AND THE MODE IS SET FOR "FILL (PUMP
UP)" ---
A PUMP IS ASSIGNED TO "LAG2"
AN INPUT NEEDS TO BE ASSIGNED TO
"LOW LEVEL" OR
THE PUMP NEEDS TO BE IN "OFF"
--- SECONDARY (BACKUP) MEASURING IS
SET FOR FLOATS ---
AN INPUT NEEDS TO BE ASSIGNED TO
"PUMPS STOP" AND
AN INPUT NEEDS TO BE ASSIGNED TO
"LEAD START
--- SECONDARY (BACKUP) MEASURING IS
SET FOR FLOATS ---
AT LEAST ONE PUMP NEEDS TO BE
SELECTED
TO RUN AS BACKUP