Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual

Page 21

Advertising
background image

Publication IASIMP-QS037A-EN-P - May 2013

19

Chapter 1

Pressure Setpoints

From the first Pressure Setpoints screen you can:

Press Pressure Setpoint to enter the desired system pressure.
Press Start Pressure to set the pressure (combined with the time

delay) at which the Lag 1 and Lag 2 pumps will come on if the
desired pressure is unable to be maintained.

View the current pressure reading (analog input must have been set

up previously).

Press Once Below Start Pressure The Next Pump Will Start in:

(Seconds) to enter the time delay in seconds between Lag pump
starts. If system pressure falls below the start set point, the Lag pump
starting is delayed by this value.

Press Off Pressure to set the system pressure point at which all of

the pumps shut off.

Press More to see the second Pressure Setpoints screen.