Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual
Page 21
![background image](/manuals/581124/21/background.png)
Publication IASIMP-QS037A-EN-P - May 2013
19
Chapter 1
Pressure Setpoints
From the first Pressure Setpoints screen you can:
– Press Pressure Setpoint to enter the desired system pressure.
– Press Start Pressure to set the pressure (combined with the time
delay) at which the Lag 1 and Lag 2 pumps will come on if the
desired pressure is unable to be maintained.
– View the current pressure reading (analog input must have been set
up previously).
– Press Once Below Start Pressure The Next Pump Will Start in:
(Seconds) to enter the time delay in seconds between Lag pump
starts. If system pressure falls below the start set point, the Lag pump
starting is delayed by this value.
– Press Off Pressure to set the system pressure point at which all of
the pumps shut off.
– Press More to see the second Pressure Setpoints screen.