Rockwell Automation 1766-L32 Pump Station Controller Quick Start User Manual

Page 21

Advertising
background image

Publication IASIMP-QS037A-EN-P - May 2013

19

Chapter 1

Pressure Setpoints

From the first Pressure Setpoints screen you can:

– Press Pressure Setpoint to enter the desired system pressure.
– Press Start Pressure to set the pressure (combined with the time

delay) at which the Lag 1 and Lag 2 pumps will come on if the
desired pressure is unable to be maintained.

– View the current pressure reading (analog input must have been set

up previously).

– Press Once Below Start Pressure The Next Pump Will Start in:

(Seconds) to enter the time delay in seconds between Lag pump
starts. If system pressure falls below the start set point, the Lag pump
starting is delayed by this value.

– Press Off Pressure to set the system pressure point at which all of

the pumps shut off.

– Press More to see the second Pressure Setpoints screen.