Create DeviceNet Network Software Files Chapter 2

10.

If your drive has not been previously used, skip to

step 12

.

11.

If your PowerFlex 70 drive has
been used previously, reset it to
factory defaults.

a. Click the Parameters tab.
b. From the Parameter 197, Reset

to Defalts pull-down menu,
choose Factory.

c. Click Apply.

12.

Use the pull-down menus to
change the following parameters.

13.

Click OK.

ID

Parameter

Required
Value

90

Speed Ref
A Sel

DPI Port 5

361

Digital In1 Sel

Not used

362

Digital In2 Sel

Not used

IMPORTANT

In this example, you do not
need to change any other
parameters because this quick
start does not include a motor.

In real-world applications, the
drive is always connected to,
and controls, a motor. In that
case, you must change
additional parameters, for
example, parameters 41…45.

Optional Selection

Required Selections