5-2

Serial Converter for use with DPI AC Drives

5.1.1 Diamond Status Indicator

!

ATTENTION: If the serial converter is transmitting control
I/O to the product (indicated by a solid green diamond LED),
the product may fault when you remove or reset the serial
converter. Determine how your product will respond before
removing or resetting a serial converter. Failure to observe
this precaution could result bodily injury and/or damage to
equipment.

Table 5.1 – Diamond Status Indicator: State Definitions

State

Cause

Corrective Action

Off

Serial converter is
not powered or in
Flash programming
mode.

• Securely connect cables.

• Apply power to the product.

• Wait while Flash is in progress.

Flashing
Green

Serial converter is
operating and not
transmitting control
I/O.

No action. Removing or resetting the serial
converter will not cause a serial fault in the
product.

Solid
Green

Serial converter is
operating and is
transmitting control
I/O.

No action.

Flashing
Red

The product has
not acknowledged
the serial
converter.

Securely connect cables.

Solid
Red

Link Failure.

• Securely connect cables.

• Replace the cable.

• Cycle power to the product.

Orange

Contact Reliance Electric Technical Support.