B-2

Serial Converter for use with DPI AC Drives

.

Action that the serial converter and product take if the serial
converter detects that DF1 serial communications are disrupted.
This setting is effective only if control I/O is transmitted through the
serial converter.

Ready No action.
Reset Module Resets the serial converter.
Set Defaults Restores the serial converter to its factory default
settings.

This parameter is a command. It will be set to “Ready” after a
“Reset Module” command or “Set Defaults” command has been
performed.

04

Comm Flt Action

Range:

0 = Fault
1 = Stop (DPI)
2 = Zero Data
3 = Hold Last

Default:

0

Type:

Read Write

Reset Required: No

!

ATTENTION: Comm Flt Action (04) lets you
determine the action of the serial converter and
connected product if communications are disrupted.
By default, this parameter faults the product. You can
set this parameter so that the product continues to
run. Precautions should be taken to ensure that the
setting of this parameter does not create a hazard
of injury or equipment damage. Failure to observe
this precaution could result in bodily injury.

05

Reset Module

Range:

0 = Ready
1 = Reset Module
2 = Set Defaults

Default:

0

Type:

Read/Write

!

ATTENTION: If the serial converter is transmitting
control I/O to the product (indicated by a solid green
diamond LED), the product may fault when you
remove or reset the serial converter. Determine how
your product will respond before removing or
resetting a connected serial converter. Failure to
observe this precaution could result in damage to,
or destruction of, the equipment.