Chapter 6 Configure and Start Up the LX-Series Linear Motor

Additional Adjustments for

Cooling Plate Option

If your linear servo motor has the cooling plate option installed, catalog number

LDC-

xxxxxx-CP, follow these steps to adjust Continuous Torque/Force Limit.

1. Click the Limits tab.
2. Set the Continuous Torque/Force Limit to reflect the motor cooling

configuration.

For linear motors, this field data entry is limited to integer values from

0…150%.

Cooling Option Used

Value

No cooling plate

0…100%

Cooling plate with forced air

0…120%

Cooling plate with forced water

0…150%

IMPORTANT Increasing or decreasing the motor continuous current rating does not

change the drives’ continuous current limiting.