Ultra-cut 400 xt – Tweco 400 XT Ultra-Cut Plasma Cutting System With Automated Gas Control User Manual

Page 188

Advertising
background image

ULTRA-CUT 400 XT

A-64

APPENDIX

Manual 0-5306

Possible cause:

• Incoming voltage is now, or was previously, too low.

o Power distribution wires or power cord too small for the load.
o Loose or high resistance connection somewhere in the power distribution or power cord connection.

• Bad connection at J62 on the System Bias board or J27 on the CCM.
• Bad connection at J61 jumper on the System Bias board.
• System Bias board defective.
• CCM defective.

Troubleshooting:

1. If the fault is L240, applying START will clear the fault unless it becomes active again. An occasional problem may be due

to incoming voltage dips or sags (voltage drops lasting from ½ cycle to as much as a minute). Usually, if the plasma is

at fault, the problem will be present all the time. After ruling out everything else we may have to attach a monitor to the

power input to determine if this is the problem.

2. Voltage can be OK when not cutting or cutting at lower currents but at higher current too much voltage may be lost due

to undersize power cord or distribution wires.

a. Measure the voltage while cutting at higher current to determine if the drop is excessive.

b. Verify all power connections are clean and secure.

c. Verify correct wires size for the current draw per the recommendations in our manual as well as the local electrical

codes.

3. It is unlikely that an open connection on the J61 jumper would result in a 240 fault, it is more likely to cause a Voltage

Mismatch fault. However, if it’s intermittent at exactly the right time, perhaps not fully plugged in, it possibly could show

up as 240. Check the jumper at J61.

4. If the incoming voltage is OK and the problem persists it may be System Bias, CCM or connection between J62 and J27.

a. If the incoming voltage is OK and D14, ACV LOW, is on or the signal “AC V LOW b” on J62-10 is “high” (about 24VDC,

relative to TP1 or J62-8 ) the System Bias board is defective.

b. If D14 is not on and signal “AC V HIGH b” on J62-10 is “low” (about 10-14VDC, relative to TP1 or J62-8) then System

Bias is OK and problem is in the CCM.

c. If J62-10 is near zero volts there may be a bad connection between J62-10 and J27-10 or J62-7 and J27-7.

241-246 Inverter Section Input Voltage Error.

The System Bias board checks for input voltage high, low or missing a phase from the power coming in from the power cord.

It is unlikely but not impossible that a problem with the incoming power could result in 241-246 codes. The 241-246 codes

more likely point to problems with the power into or within a single inverter section or in the case of missing phase it may

be the contactor that supplies up to 3 inverter sections.

Once the input contactors close, applying voltage to the inverters, they test for input too high or too low and for missing

phase. When the input voltage is in the correct range, a green LED, D4, named READY, lights on the left side of the main

inverter board. If D4 is not on, either the input voltage is out of range or the inverter is defective.

You can still get the 241-246 code with a missing phase with the READY LED on. The LED will be going on and off rapidly

but appears to the eye to be on. In this case you can measure the signal on the ribbon cable. The signal previously called

READY is now called AC_INPUT_FLT. It is a differential signal on pins 1(+) & 2(-) of the inverters 30 pin ribbon cable. If the

AC input is correct you should read 5-6V between the pins. If AC_INPUT_FLT is true voltage on pins 1 & 2 will be less than 2V.

Some of the other faults such as Inverter Fault and Over Temperature also set the AC_INPUT_FLT (not Ready). However, they

will latch on associated LEDs or set different fault codes. In the event of an Input Voltage Fault the CCM does not remove

power from the inverter.

Advertising