Beacon Exit Device

Installation and Wiring Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

Beacon

TB1

Termination Description

1

+

DC IN

Beacon Input Power: 24VDC (1.0 Amp minimum) from FACP (Fire Alarm Control Panel).
Beacon will operate from 16 to 33VDC.

2

-

3

+

IN/CC

Beacon Alarm input from FACP. Two choices: NAC IN (NAC) 24VDC (8 to 33VDC) or dry contact
closure (CC) sets Beacon into Alarm Mode. Set NAC/CC switch on Beacon module to NAC or CC
according FACP wiring application.

4

-

5

+

RET

Additional Alarm signal connections for interconnectiing multiple Beacon rail assemblies

6

-

7

+

SIL

Beacon Silence input signal from FACP. Purpose is to stop Beacon audible (voice messages) during
a fire alarm so emergency personnel can listen to their radios. A valid silence condition occurs when
24vdc (8 to 33VDC) signal is present on the Silence Input for >= 500 msec, and is then removed for
>= 125 msec.

8

-

Wiring diagram examples reflect ElectroLynx system application.
For additional ElectroLynx product (door harnesses, power transfer devices, and frame harness) information and

requirements, refer to McKinney Power Transfer Device Catalog.

ElectroLynx power transfer device and harness requirement for all Beacon applications is QC12.

SECTION III: Beacon Wiring Examples

Simplified Diagram of an In-building Commercial Fire Alarm System

(excludes fire suppression and central station controls)