Beacon Exit Device

Installation and Wiring Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

Trouble Conditions and Corrective Actions

Fault Condition

Fault

Corrective Action

Blink Amber trouble LED
using repeating Blink *1
pattern.

*A 1 second blink with a 5
second pause.

Input power under
16VDC**

Correct input voltage to 24VDC (nominal);
(operates from 16-33VDC)

Blink Amber trouble LED
using repeating Blink 2*
pattern.

*Two 1 second blinks with a
5 second pause.

Laser over current
condition**

Replace Beacon Insert Assembly

Blink Amber trouble LED
using repeating Blink 3*
pattern.

*Three 1 second blinks with
a 5 second pause.

Motor over current
condition**

Replace Beacon Insert Assembly

Blink Amber trouble LED
using repeating Blink 4*
pattern.

*Four 1 second blinks with
a 5 second pause.

Invalid DIP switch
configuration

All DIP switches are OFF**

Refer to DIP Switch Setting/Configuration
Section II.4 for valid switch selections.

Blink Amber trouble LED
using repeating Blink 5*
pattern.

*Five 1 second blinks with a
5 second pause.

Key switch stuck error**

If key switch is detected as
turned for >= 30 seconds.

Inspect operation of cylinder cam with
Beacon plastic switch actuator.

Free possible obstruction or replace
Beacon Insert Assembly if inoperable.

**

Disables all audible and visual notification alerts.