Beacon Exit Device

Installation and Wiring Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

SECTION VI: BEACON Modes of Operation

Mode

Description

What Happens

Initiated by:

Deactivated by

Active/

Standby

This mode can be

considered the idle state.

(Notification Alarms are shut

off in this mode)

Green LED is ON.

This is the default power on

state.

(Beacon is connected and

powered)

Beacon comes out of

Active Mode whenever

another mode is triggered

Test

A temporary state where the

Beacon will perform a self-

test.

Audio messaging will

play every message

once, followed by

“Test Mode Complete”

message.

All Visual Notification

including the high

brightness LEDs will

flash and laser cone

will illuminate for four

seconds.

Rotating key switch clockwise

(to stop) for five seconds,

then releasing

Automatically returns to

Active Mode after cycling

Alarm

Beacon alarms in response

to fire alarm system outputs.

Audio messaging will

play according to dip

switch settings.

High Brightness LEDs

and laser cone will

illuminate according to

dip switch settings.

Fire alarm system outputs

Automatically returns to

Active Mode when:

• key switch is fully

rotated for two sec-

onds, then released

• FACP alarm input is

inactive for two or

more seconds

See Silence Mode (below)

Silence

Overrides audible notification

during a fire alarm so that

emergency personnel can

listen to their radios.

Audio messaging will

not play.

High Brightness LEDs

and laser cone will

illuminate according to

dip switch settings.

A silence condition can occur

only during ALARM MODE:

When Beacon’s Silence

input receives a valid

silence condition from FACP,

8-33VDC is present on the

Silence Input for >= 500ms,

and then removed for >=

125ms

Beacon alarm input is

inactive for two or more

seconds

NOTE: Audio messages

return if Silence input to

Beacon receives 8-33VDC

signal from FACP

When key switch is rotated

fully clockwise (to stop)

for two seconds, then

released, Alarm Mode is

turned off and unit returns

to Active state (Silence

Mode is turned off)

Trouble

Problem with operation,

setup or wiring

Blinking Amber LED

Internal diagnostics

See following section on

trouble conditions