System messages – Dell PowerVault 770N (Deskside NAS Appliance) User Manual
Page 22
6
+2.5V is not good.
OFF
BLINK ON
ON
OFF
7
+3.3V is not good.
OFF
BLINK ON
ON
ON
8
+3.3V_PCI is not good.
ON
BLINK OFF
OFF
OFF
9
+5V is not good.
ON
BLINK OFF
OFF
ON
10 System POWERGOOD missing. Bad U6009.
ON
BLINK OFF
ON
OFF
11 Standby POWERGOOD missing. Bad +5V_AUX or +1.8V_AUX.
ON
BLINK OFF
ON
ON
12 VRM_P1 is not good.
ON
BLINK ON
OFF
OFF
13 VRM_P2 is not good.
ON
BLINK ON
OFF
ON
3 - NOPOST NO VIDEO (chipset)
1
CPU POR is not high. North bridge chip on the planar has likely failed. Replace
planar.
OFF
OFF
BLINK OFF
ON
2
ICH3 PCI Reset is not high. ICH3 chip on the planar has likely failed. Replace
planar.
OFF
OFF
BLINK ON
OFF
System Messages
System messages appear on the console during POST to notify you of a possible problem with the system. If you are
performing console redirection, system messages will appear on the remote console.
lists the system messages
that can occur and the probable cause for each message.
NOTE:
If you receive a system message that is not listed in
, check the documentation for the application
program that is running when the message appears or the operating system's documentation for an explanation of the
message and recommended action.
Table 3-12. System Messages
Message
Causes
Corrective Actions
Address mark not found
Faulty CD/diskette
drive subsystem or
hard-drive
subsystem; faulty
system board.
Replace the faulty drive(s) (see "
" and "
"). If the problem persists, replace
the system board (see "
Alert! All memory in the system
must have the same primary
SDRAM width. The following
memory DIMMs have been
disabled: DIMMnX.
Memory modules
installed are not the
same type and size
in all banks; faulty
memory module(s).
Ensure that all banks contain memory modules of the same
type and size and that they are properly installed. If the
problem persists, replace the faulty memory module(s) (see
").
Alert! Unsupported memory or
incomplete sets in the
following bank(s): Bank DIMMnX
Memory modules
installed in the
specified bank(s) are
not the same type
and size; faulty
memory module(s).
Amount of available memory
limited to 256 MB!
OS Install Mode is
enabled in the
System Setup
program.
Disable OS Install Mode in the System Setup program (see
Using the System Setup Program
").
Auxiliary device failure
Loose or improperly
connected mouse or
keyboard cable;
faulty mouse or
keyboard.
Check the mouse and keyboard cables and connectors. If the
problem persists, replace the mouse and keyboard. If the
problem persists, replace the system board (see "