CHAPTER 9 8454

9-14

D569-W02 May-2003

f.

Abnormal noise from the blower motor

In case of the generation of abnormal noise from
the blower motor and the poor revolution, change
the blower motor with the new one.

In case of generation of the abnormal noise caused
by the foreign material in the blower or by the poor
tightening, pay attention to work.

B. EARLY FINDING OF TROUBLE

SHOOTING

a . Poor Air-Conditioning

1) Fan motor does not revolve.

Check the fuse of air-conditioner.

Check the earth of fan motor and
the missing of key boss.

When checking 2 leads coming
from the motor in the circuit tester,
the current does not transmit.

When checking whether or not the
resister transmits the current by
circuit tester, the current does not
transmit.

Check the revolution of fan by
operating the fan switch in order.

Replacement

Repair the cutting section or
connect correctly.

Replacement

Replacement

Replacement

Causes

Checking Methods

Action

1. Fuse cutting

2. Wiring cutting or poor

connection

3. Failure of fan motor

4. Wire cutting of resister

5. Failure of fan switch

2) Fan motor is normal but the capacity of wind is small.

Contamination of vaporizer

Check the assembly status of
cooling unit case.

Check whether the vaporizer is
frozen with a circuit tester.

Removal of obstacles, cleaning

Modification or adjustment

Replacement

Causes

Checking Methods

Action

1. Obstacles in the inlet of suction

of vaporizer

2. Air leakage

3. Poor thermo-switch

3) The extract airflow and revolution of compressor is normal but poor air-conditioning.

After 5 ~ 10 min. operation of air-
conditioner, touch the high/low
pressure pipe by hand. Observe
the flow of refrigerant of sight
glass and check the amount of
refrigerant.

Rarely the difference of tempera-
ture between high pressure side
and low pressure side. The flow of
bubble is seen in the sight glass
or the flow of foggy state is a little
seen.

The pressure of high-pressure
side is high and the bubble of
sight glass is not seen when we
try to cool the compressor with
water.

Repair the leaked part and
supplement by the proper amount.

Exhaust the refrigerant little by
little till you can see the bubble in
the sight glass.

Causes

Checking Methods

Action

1. Excess/lack of refrigerant

2. Lack of refrigerant

3. Over supplement of refrigerant