Cabin system 9-17 – Cub Cadet 8454 User Manual

Page 331

Advertising
background image

CABIN SYSTEM

9-17

D569-W02 May-2003

569W921A

569W922A

•

When exhausting the refrigerant, ex-
haust it to the low pressure side slowly
and check the pressure graduation
and sight glass to check the amount
of refrigerant.

•

Pay attention to the contamination of
radiator.

2. Excess of refrigerant charging

Status: Not cool

Phenomena:

- Pressure rising by overcharging of refrigerant

- Lack of cooling of the compressor

Cause:

- Pressure rising by overcharging of refrigerant

- Lack of cooling of the compressor

Action:

- Clean the compressor

- Check and adjust fan belt or compressor motor

- Check the amount of refrigerant

3. Air mixing (lack of vacuum working)

Status: Not cool

Phenomena:

- The pressure of high /low pressure side is high.

- The pipe of low pressure side is not cold.

Cause: Air mixing in the refrigerating cycle. In case
of no vacuum working, the graduation is shown on
the left figure.

Action: When charging the refrigerant by making a
vacuum, check the guide.

In case of operating for a long time in the state of air
mixing, replace the receiver drier.

2.5 ~ 3.5 kgf/cm

2

35.6 ~ 49.8 psi

20 kgf/cm

2

284.5 psi

Low excess of

refrigerant charging

High excess of

refrigerant charging

2.5 ~ 3.5 kgf/cm

2

35.6 ~ 49.8 psi

23 ~ 24 kgf/cm

2

327.1 ~ 341.3 psi

Low air mixing in the

refrigerating cycle

High air mixing in the

refrigerating cycle