CABIN SYSTEM

9-19

D569-W02 May-2003

569W926A

3. The refrigerant does not circulate.

Status: not cool (sometimes cool)

Phenomena:

- The pressure of low pressure side is negative

and the pressure of high pressure side shows
the pressure 5 ~ 6 kg/cm

2

.

- Frost or dew forming in the receiver drier or the

front/rear pipe connection section of extension
valve.

Cause:

- The cycle is closed by moisture freezing or dust

in the refrigerating cycle.

- The cycle is blocked due to the poor wound box

of extension valve.

Action: Stop the operation once to check the clog-
ging by moisture or dust. If found the moisture, do
the vacuum working.

- Detach the extension valve and remove the dust

by air.

- Replace the receiver drier.

- Charge the proper amount of refrigerant.

1.0332 kgf/cm

2

14.696 psi

5 ~ 6 kgf/cm

2

71.1 ~ 85.3 psi

Low poor circulation

of refrigerant

High poor circulation

of refrigerant