CHAPTER 9 8454

9-18

D569-W02 May-2003

569W923A

569W924A

569W925A

4. Poor extension valve

Status: Not cool

Phenomena:

- The pressure of high /low pressure side is high.

Cause: Poor extension valve, poor control of refrig-
erant flow rate by poor assembling of the wound
box.

Action: Check the assembly status, location and in-
sulation status of the wound box. With no failure,
replace the extension valve.

b. Not Cool (some times cool)

1. Poor compression of the compressor

Status: Not cool

Phenomena:

- The pressure of low pressure side is high and

the pressure of high pressure side is very low.

- When stopping the operation, the pressure of

h i g h / l o w p r e s s u r e s h a l l b e t h e s a m e
immediately.

Cause: Poor gasket of compressor, poor compres-
sor caused by the broken suction valve.

Action: Disassemble and repair the compressor.

2. Moisture mixing

Status: Sometimes cold, sometimes not cold

Phenomena:

- The pressure of low pressure side is sometimes

negative or sometimes returning normal.

Cause: The moisture inside refrigerating cycle is
frozen which makes the cycle closed in the exten-
sion valve and return to the normal by melting of
ice.

Action: Replace the receiver drier.

Repeat the vacuum working 2 ~ 3 times. Charge
the proper amount of refrigerant.

2.3 kgf/cm

2

32.7 psi

19 ~ 20 kgf/cm

2

270.2 ~ 284.5 psi

Low poor extension

valve

High poor extension

valve

4 ~ 6 kgf/cm

2

56.9 ~ 85.3 psi

7 ~ 10 kgf/cm

2

99.6 ~ 142.2 psi

Low poor compression

of the compressor

High poor compres-

sion of the compressor

- ~ 1.5 kgf/cm

2

- ~ 21.3 psi

6 ~ 16 kgf/cm

2

85.3 ~ 227.6 psi

Low moisture mixing in

the refrigerating cycle

High moisture mixing

in the refrigerating cycle