3-6 Setting the Tolerance Setting Value

3-16

3

B

a

sic O

perat

io

ns

IB-E

2-point tuning

With this method, the median value of the good target and defective target is set as the
tolerance setting value when there are good target and HIGH/LOW defective target.

1

Press the / button several times on the main screen. Then display the
HIGH setting value on the sub display (lower level).

"Sub Display (Lower Level)" (page 3-4)

2

Measure the good target and press the [SET] button. (HIGH side 1st point
confirmation operation)

The internal measurement value (R.V.) is imported as a good target measurement
value.
[Hiset] is displayed on the main display (upper level).

3

Measure the HIGH side defective target and press the [SET] button. (HIGH
side 2nd point confirmation operation)

The internal measurement value (R.V.) is imported as a measurement value for
HIGH side defective target.
After [set] blinks on the main display (upper level), the judgment value (P.V.) is
displayed.
On the sub display (lower level), the median value of the good target value (1st point)
imported on step 5 and HIGH defective target value (2nd point) is displayed.
Setting the HIGH setting value (upper limit) is complete.

4

Press the button once and display the LOW setting value on the sub
display (lower level).

Point

2-point tuning cannot be performed if the internal measurement
value (R.V.) is [
-----], [FFFF] or [-FFFF]. If performed, [no.uAL] will
blink several times on the main display.

GO



LASER

BANK

0

1

2

3

HI

LO

R.V. ANALOG

HI

SHIFT

ZERO SHIFT

TIMING

LO

ALIGNMENT



HOLD

CALC

CHECK

[HI]

ON

HIGH setting value

GO

HOLD

CALC

CHECK



LASER

BANK

0

1

2

3

HI

LO

R.V. ANALOG

HI

SHIFT

ZERO SHIFT

TIMING

LO

ALIGNMENT



LOW setting value

[LO]

ON

Advertising