KEYENCE N-410 User Manual

Page 133

Advertising
background image

7-17

7-3

Settings

PLC

Link

7

QJ71C24(N/-R2)

Set the communication conditions with GX-Developer.
("I/O assignment settings" under "PC parameters")

("Switch settings" under "I/O assignment settings" under "PC parameters")

Type

Intelligent

Model

Attachments

Points

32

Header XY

Header input signal number (hexadecimal) for the
target unit

Setting switch

Setting item

Setting

Switch 1 (ch1)
or
Switch 2 (ch2)

Operation settings

Independent

Data bits

8 bit

Parity

Odd (o)

Stop bit length

1 bit

Checksum

Yes

Write during RUN

Yes

Settings changeable

Yes

Communication speed

9600 bit/s

Switch 1 (ch1)
or
Switch 2 (ch2)

Communication protocol

MC protocol format 4

Switch 5

Station number setting

0