Page 102

GATEWAY COMMUNICATIONS MANUAL
102
Binary Value (STAT):
6. Range
Restrictions:
active_text
change_of_state_count
description
elapsed_active_time
inactive_text
minimum_off_time
minimum_on_time
notification_class
time_delay
limited to 50 octets in length
0 to 4294967295
limited to 50 octets in length
0 to 4294967295
limited to 50 octets in length
0 to 4294967295
0 to 4294967295
must be valid
notification_class
0 to 4294967295
16.5 BINARY VALUE (MODULE ALARM)
Binary Value (MODULE ALARM):
1. Creatable?
NO
2. Deletable?
NO
3. Optional
Properties
Supported:
acked_transitions
alarm_value
description
event_enable
event_time_stamps
notification_class
notify_type
time_delay
4. Writeable
Properties:
alarm_value
event_enable
notification_class
notify_type
out_of_service
time_delay
5. Proprietary
Properties:
None
6. Range
Restrictions:
notification_class
time_delay
must be valid
notification_class
0 to 4294967295