GF-122 AERCO XPC GATEWAY

137

Modbus-To-BACnet Protocol Mapping

1 BMS/BMS II, 12 C-More Boilers (Continued)

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

BACnet

Type:ID

Blr Addr 4

01-Fire Rate Out

boilerstate_4

30009/4

AV:70

02-Active Setpoint

effectsetpt_4

30017/4

AV:71

03-Net Remote Setpt

setpt_4

40001/4

AV:72

05-Fire Rate In

boilerload_4

30018/4

AV:73

06-Outlet Temp

localsuptemp_4

30003/4

AV:65

07-Display Code

dispcode_4

30001/4

AV:66

08-Unit Status

unitstat_4

30002/4

AV:67

09-Run Cycles

runcycles_4

30012-30013/4

AV:68

10-Run Hours

runhours_4

30014-30015/4

AV:69

Deg F or Deg C

m114_4

BV:10

Use Temp Scaling

m101_4

BV:11

Blr Addr 5

01-Fire Rate Out

boilerstate_5

30009/5

AV:80

02-Active Setpoint

effectsetpt_5

30017/5

AV:81

03-Net Remote Setpt

setpt_5

40001/5

AV:82

05-Fire Rate In

boilerload_5

30018/5

AV:74

06-Outlet Temp

localsuptemp_5

30003/5

AV:75

07-Display Code

dispcode_5

30001/5

AV:76

08-Unit Status

unitstat_5

30002/5

AV:77

09-Run Cycles

runcycles_5

30012-30013/5

AV:78

10-Run Hours

runhours_5

30014-30015/5

AV:79

Deg F or Deg C

m114_5

BV:12

Use Temp Scaling

m101_5

BV:13

Blr Addr 6

01-Fire Rate Out

boilerstate_6

30009/6

AV:90

02-Active Setpoint

effectsetpt_6

30017/6

AV:91

03-Net Remote Setpt

setpt_6

40001/6

AV:92

05-Fire Rate In

boilerload_6

30018/6

AV:84

06-Outlet Temp

localsuptemp_6

30003/6

AV:85

07-Display Code

dispcode_6

30001/6

AV:86

08-Unit Status

unitstat_6

30002/6

AV:87

09-Run Cycles

runcycles_6

30012-30013/6

AV:88

10-Run Hours

runhours_6

30014-30015/6

AV:89

Deg F or Deg C

m114_6

BV:14

Use Temp Scaling

m101_6

BV:15