GF-122 AERCO XPC GATEWAY

77

3. Comm selector DIP Switches 1 - 8 are all OFF.

4. Port 1a is the only port that speaks BACnet over ARC156. Connect the communications wiring to Port

1a in the screw terminals labeled Net +, Net -, and Gnd. See the illustration below.

NOTE

USE THE SAME POLARITY THROUGHOUT THE NETWORK SEGMENT.

Wire specifications

:

• 22 AWG, low-capacitance, twisted, stranded, shielded copper wire
• 2000 feet (609.60 meters) before needing a Repeater.
• If the XPC is at either end of a network segment, connect a BT485 to the XPC.

5. Turn on the XPC's power.

6. Set the correct network number to the unique BACnet ARC156 network at the site.