GF-122 AERCO XPC GATEWAY

27

1.10.6 AERCO XPC to Boiler Management System (BMS)

AERCO XPC TO BOILER MANAGEMENT SYSTEM

(BMS)

XPC Part Number:

“25024-1” for 1 BMS and up to 4 C-MOREs, or “25024-2” for 1 BMS and up to 12 C-MOREs , or

“25024-4” for 1 BMS and up to 4 MLX Boilers (with BCMs), or 25024-5 for 1 BMS and up to 8 C-MOREs

XPC Port 2 to BMS Port JP12:

Wire to XPC Port 2

 “TX” to “RXD”, “RX” to “TXD”, “Signal Ground” to “GND”, and Shield connected at

one end only to the BMS at the “SHIELD” input. Jumper “DTR” and “DCD” on port 2.

Place 4-position jumper on EIA-232 (two top rows);

Place 2-position jumper on 2W;

XPC Software Setup:

Modbus Response Time = 20(x100 msec) (default);

BMSII RS232 Software Setup:

RS232 Mode = Modbus Slave; RS232 Baudrate = 9600; Modbus Address = 128; Modbus Pass Thru =
Enabled (if reading information from boilers, else leave Disabled);

BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES

AERCO XPC

BMS

Port 1a Port 2

RS232 RS485

RS232

m

odbu

s

JP12 JP11