Page 44

GATEWAY COMMUNICATIONS MANUAL
44
2.7.2 Direct Drive Control and Monitoring
Direct Drive Control of the C-More Boiler Controller is no longer allowed via the AERCO XPC Gateway.
2.7.3 Remote Setpoint Control
Remote Setpoint Control of the C-More Boiler Controller is set up as follows:
1. Enter and store a valid Comm Address using the procedures in subsection 2.7.1.
2. Scroll through the Configuration Menu and change the following menu items to the settings shown:
MENU OPTION
SETTING
Boiler Mode
Remote Setpoint
Remote Signal
Network
3. The C-More Controller is now set for Remote Setpoint operation via the RS485 (Modbus) Network.
AERCO recommends that the Setpoint Limiting feature in the Configuration Menu be enabled. Also,
ensure that the Failsafe Mode setting is set to the desired setting (Shutdown or Constant Setpoint) in the
event that the Network signal is lost.