1.10.8 AERCO XPC to C-More

AERCO XPC TO C-MORE

XPC Part Number:

25024-1 or 63046-1 for 1 BMS and up to 4 C-MOREs; 25024-2 for 1 BMS and up to 12 C-MOREs; 25024-5 for 1
BMS and up to 8 C-MOREs

XPC Port 2 to C-MORE (I/O Box) RS485:

Wire to XPC Port 2

 “Net+” to “RS485+”, “Net-” to “RS485-”, and Shield connected at one end only - to the C-

MORE (I/O Box) at the “SHLD” input.. Daisy chain to the other units..

Place 4-position jumper on EIA-485 (two bottom rows);

Place 2-position jumper on 2W;

XPC Software Setup:

Modbus Response Time = 2 (x100 msec); (Must be changed using AppLoader Software and Programmer Cable.)

C-MORE Setup:

For Monitor Only

 “Comm Address” = (boiler address starting with “1”);

For Monitor and Remote Setpt Control via Modbus

 Set “Comm Address” as above; Set “Boiler Mode” to

“Remote Setpt”; Set “Remote Signal” to “Network”.

BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES

AERCO XPC

C-MORE

Port 1a Port 2

RS485

RS485