SECTION 30 C-MORE BOILER CONTROLLER STATUS & FAULT

MESSAGES

Table 11 C-More Controller Status and Fault Messages

Code

MESSAGE

DESCRIPTION

1

DISABLED

HH:MM pm MM/DD/YY

Displayed if ON/OFF switch is set to OFF. The display also
shows the time and date that the unit was disabled.

2

STANDBY

Displayed when ON/OFF switch is in the ON position, but there
is no demand for heat. The time and date are also displayed.

3

DEMAND DELAY

XX sec

Displayed if Demand Delay is active. The “XX” represents
changing display digits.

4

PURGING

XX sec

Displayed during the purge cycle during startup. The duration
of the purge cycle counts up in seconds. The “XX” represents
changing display digits.

5

IGNITION TRIAL

XX sec

Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds. The “XX” represents
changing display digits.

6

FLAME PROVEN

Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place of
flame strength.

7

WARMUP

XX sec

Displayed for 2 minutes during the initial warm-up only. The
“XX” represents changing display digits.

8

HIGH WATER TEMP

SWITCH OPEN

The High Water Temperature Limit Switch is open.

9

LOW WATER

LEVEL

The Water Level Control board is indicating low water level.

10

LOW GAS

PRESSURE

The Low Gas Pressure Limit Switch is open.

11

HIGH GAS

PRESSURE

The High Gas Pressure Limit Switch is open.

12

INTERLOCK

OPEN

The Remote Interlock is open.

13

DELAYED

INTERLOCK OPEN

The Delayed Interlock is open.

14

AIRFLOW FAULT

DURING PURGE

The Blower Proof Switch opened during purge.

15

SSOV FAULT

DURING PURGE

The SSOV switch opened during purge.

16

PRG SWTCH OPEN

DURING PURGE

The Purge Position Limit switch on the Air/Fuel valve opened
during purge.