Modbus-To-LonWorks Protocol Mapping

1 BMS/BMS II, 8 C-More Boilers

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

SNVT

#

SNVT NAME

SNVT

Element

#

Direction

Prio Auth Ack

Blr Addr 1

01-Fire Rate Out

boilerstate_1

30009/1

41

nvoBlrState1

incremental
count (9)

0

Output (non-
polled)

02-Active Setpoint

effectsetpt_1

30017/1

42

nvoEffSetpt1

incremental
count (9)

0

Output (non-
polled)

03-Net Remote
Setpt

setpt_1

40001/1

43

nviSetpt1

incremental
count (9)

0

Input (non-
polling)

05-Fire Rate In

boilerload_1

30018/1

45

nvoBlrLoad1

incremental
count (9)

0

Output (non-
polled)

06-Outlet Temp

localsuptemp_1

30003/1

46

nvoLocSupTmp1

incremental
count (9)

0

Output (non-
polled)

07-Display Code

dispcode_1

30001/1

47

nvoDispCode1

incremental
count (9)

0

Output (non-
polled)

08-Unit Status

unitstat_1

30002/1

48

nvoUnitStat1

incremental
count (9)

0

Output (non-
polled)

09-Run Cycles

runcycles_1

30012-30013/1

49

nvoRunCycles1

51

0

Output (non-
polled)

10-Run Hours

runhours_1

30014-30015/1

50

nvoRunHours1

51

0

Output (non-
polled)

Deg F or Deg C

m114_1

0

disabled NV
(0)

0

Input (non-
polling)

Use Temp Scaling

m101_1

0

disabled NV
(0)

1

Input (non-
polling)

Blr Addr 2

01-Fire Rate Out

boilerstate_2

30009/2

51

nvoBlrState2

incremental
count (9)

0

Output (non-
polled)

02-Active Setpoint

effectsetpt_2

30017/2

52

nvoEffSetpt2

incremental
count (9)

0

Output (non-
polled)

03-Net Remote
Setpt

setpt_2

40001/2

53

nviSetpt2

incremental
count (9)

0

Input (non-
polling)

05-Fire Rate In

boilerload_2

30018/2

55

nvoBlrLoad2

incremental
count (9)

0

Output (non-
polled)

06-Outlet Temp

localsuptemp_2

30003/2

56

nvoLocSupTmp2

incremental
count (9)

0

Output (non-
polled)

Page 1 of 7