Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 126

GATEWAY COMMUNICATIONS MANUAL
126
Table 9 AERCO Electronic Control System (ECS) Point Definitions
Equip.
Point Name
BAS Modbus
Data Addr
AC-105 Point
Name
Reg.
Type
Modbus Data
Addr (Hex/Dec.)
Units (Range)
Electric Valve (ECS)
01-Cntl Output
Signal
30004
OP (Control
Output Signal)
Input
0x0003 / 3
% (0 to 100)
02-Setpoint
30006
w.SP (Setpoint)
Input
0x0005 / 5
°F (40 to 180)
03-RmSetpt
40027
Remote Input
Comms Access
parameter(Setpoi
nt)
Holding
0x001A / 26
°F (40 to 180)
04-Outlet Temp
30002
Top Value (Outlet
Temp)
Input
0x0001 / 1
°F (40 to 205)
05-FBk Sensor
Temp
30290
Li1 (Feedback
Sensor Temp)
Input
0x0121 / 289
°F (40 to 180)
06-Over Temp Alarm
30075
AL 1 (Over Temp
Alarm)
Input
0x004A / 74
Enum (0,1) 0 = Safe, 1 =
Alarm
07-Flow Rate
30291
Li2 (Flow)
Input
0x0122 / 290
GPM