1.10.2 BACNET MS/TP to AERCO XPC
BACNET MS/TP TO AERCO XPC
XPC Port 1a:
•
Wire to Port 1a
+ to “Net+”, - to “Net-”, and Shield connected at one end only. If to XPC then to
“Shield” connector.
8-Position Dipswitch:
•
Dipswitch 1,2 set to BACNET MS/TP communication baud rate;
•
Dipswitch 3 = Off (B.A.S. on port 1);
•
Dipswitch 4 = On (EIA485 on port 1);
•
Dipswitch 5-8 = Off, Off, Off, Off (for bacnet ms/tp (m));
Rotary Address Switches:
•
2 Rotary Address Switches set to Bacnet ID address for the XPC)
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES.
AERCO XPC
BACNET
MS/TP
Port 1a Port 2