GF-122 AERCO XPC GATEWAY

65

7 6 5 4 3 2 1

Y2

Y2

Y3

Y4

Y1

SW1

A1

I

0

M

O

D

B

US

A

(

-)

M

O

DB

US

B

(

+

)

BCM FRONT VIEW

Figure 4-2. BCM Modbus (RS485) Connections

4.2 BCM WIRING CONNECTIONS TO AERCO XPC GATEWAY

XPC Port 2 is normally used to connect to AERCO equipment, except when the controlling BAS is
utilizing a LonWorks SLTA module, or communicating via BACnet PTP. In this case, Port 1a of the XPC
must be used to connect AERCO equipment. Therefore, follow the appropriate wiring instructions in
subsection 4.2.1 (Port 2) or 4.2.2 (Port 1a) as applicable.

4.2.1 BCM Wiring Connections to XPC Port 2

When the controlling BAS is utilizing BACnet MS/TP, Johnson N2 or LonWorks protocol without an
SLTA, use XPC Port 2 as follows:

1. On the XPC Gateway, position the EIA-232/EIA-485 and 2W/4W jumpers to EIA-485 and 2W

respectively as shown in Figure 4-3.

EIA-485

EIA-232

2W

4W