Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual

Page 83

Advertising
background image

GF-122 AERCO XPC GATEWAY

83

.

3. Set the Comm Selector DIP Switches 1 - 8 for baud rate, port number, wiring, and protocol:

• Set the Comm Selector DIP Switches 1 and 2 for 9600 bps.

NOTE

USE THE SAME BAUD RATE FOR ALL DEVICES ON THE NETWORK
SEGMENT.

• Set Comm Selector DIP Switch 3 to OFF for BAS Port 1.
• Set Comm Selector DIP Switch 4 to ON for EIA-485 2-wire.
• Set the Comm Selector DIP Switches 5 through 8 for N2.

The following example shows the DIP Switches set for 9600 baud, Port 1a, and N2.

4. Connect the communications wiring to Port 1a. Connect to Net+, Net-, and Gnd.