Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 124
Advertising
GATEWAY COMMUNICATIONS MANUAL
124
08-Num Boilers
Online
30009
Total Boilers On
Line
Input
0x0008 / 8
(0 to 40) BMS
(0 to 32) BMSII
09-Last Blr Fired
30017
Last Boiler Fired
Input
0x0010 / 16
(1 to 40) BMS
(1 to 32) BMSII
10-Boiler 1 Status
30018
Boiler 1 Status
(PWM Boiler 1)
Input
0x0011 / 17
Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
11-Boiler 2 Status
30019
Boiler 2 Status
(PWM Boiler 2)
Input
0x0012 / 18
Same As Above
12-Boiler 3 Status
30020
Boiler 3 Status
(PWM Boiler 3)
Input
0x0013 / 19
Same As Above
13-Boiler 4 Status
30021
Boiler 4 Status
(PWM Boiler 4)
Input
0x0014 / 20
Same As Above