Gateway communications manual, C-mores connected to xpc port 1a – AERCO XPC GATEWAY Communications User Manual

Page 46

Advertising
background image

GATEWAY COMMUNICATIONS MANUAL

46

NOTES:

1. PORT 2 CONNECTIONS AND JUMPER POSITIONS
WILL DEPEND ON THE AVAILABLE PORTS ON THE
BAS BEING USED. SEE DETAIL “A”.

2. THE LAST C-MORE BOILER ON THE RS485 LOOP
MUST HAVE ITS TERMINATION RESISTOR (TERM)
TURNED ON. ALSO, BIAS (BIAS1, BIAS2) MAY BE
REQUIRED. CHECK WITH THE BAS MANUFACTURER.

+

-

RS485
COMM

(P/O I/O BOX)

C-MORE

NETWORK BOILER 1

-

+

RS485
COMM

P/O I/O BOX

C-MORE

NETWORK BOILER 2

TO OTHER NETWORK

BOILERS

(SEE NOTE 2)

XPC GATEWAY

PORT

1a

NET +

NET -

SHLD

EIA-232

EIA-485

2W

4W

TO BAS

(SEE NOTES)

PORT

2

S

EE N

OTE

1

JUMPERS

2W

4W

232

Net +

Net -

N/C

N/C

Tx +

Tx

Tx -

Rx

DTR

Rx -

DCD

SIGNAL GROUND

Rx +

Port 2

DETAIL “A”

C-MOREs CONNECTED TO XPC PORT 1a

Figure 2-9. C-More Controller Sample Network Diagrams (Sheet 2 of 2)