INSTALLATION

2-4

SHELL

CAP

PARTIAL TOP VIEW OF BOILER

FOR INSTALLATION OF PRESS./TEMP. GAUGE

PART NO. 122994-1 (PRESS. RANGE 0 – 75 PSI)

SYSTEM

SUPPLY

1/2" x 1 /4"

REDUCING BUSHING

PRESS./TEMP. GAUGE

Figure 2.5a

Pressure /Temperature Gauge Installation

SHELL

CAP

PARTIAL TOP VIEW OF BOILER

FOR INSTALLATION OF PRESS./TEMP. GAUGE

PART NO. 122994-2 (PRESS. RANGE 0 – 200 PSI)

PART NO. 122994-3 (PRESS. RANGE 0 – 300 PSI)

SYSTEM

SUPPLY

1/2" NIPPLE

1/2" UNION

PRESS./TEMP. GAUGE

Figure 2.5b

Pressure/Temperature Gauge Installation

2.3.5 CONDENSATE PIPING

The KC Boiler is designed to condense.

Therefore, the installation site must include

suitable provisions for condensate drainage or

collection. A stainless steel condensate cup is

separately packed within the unit’s shipping

container. To install the condensate cup,

proceed as follows:
1. Remove the left side panel and only the left

half of the rear cover to provide access to the

exhaust manifold and burner (Figure 2.6).

2. Insert the 1-3/4 inch manifold drain hose into

the condensate cup. Allow the cup to rest on

the floor directly beneath the manifold drain

hole (Figure 2.6).

3. Attach a length of 3/4 inch I.D. polypropylene

tubing to the condensate cup drain tube and

route it to a floor drain. If a floor drain is not

available, a condensate pump can be used to

remove the condensate to drain. The

condensate drain line must be removable for

routine maintenance. Therefore, DO NOT hard-

pipe.

4. Replace the rear cover and side panel on the

unit.

TEMPERATURE SENSOR

EXHAUST

MANIFOLD

CONDENSATE

DRAIN

BURNER

HOSE CLAMP

1-3/4" O.D. x 8-1 /2 “ LG.

SILICONE HOSE

5/8" O.D. TUBE CONN.

CONDENSATE CUP

PLACED ON FLOOR

Figure 2.6

Condensate Drain System Location

2.4. GAS SUPPLY PIPING

The AERCO

Gas Fired Equipment Gas Compo-

nents and Supply Design Guide (GF-1030) must be

consulted before any gas piping is designed or

started.

WARNING!

DO NOT USE MATCHES, CANDLES,

FLAMES OR OTHER SOURCES OF

IGNITION TO CHECK FOR GAS LEAKS

.

CAUTION!

Soaps used for gas pipe leak testing can be

corrosive to metals. Piping must be rinsed

thoroughly with clean water after leak

checks have been completed.

NOTE:

All gas piping must be arranged so that it

does not interfere with removal of any

cover, inhibit service or maintenance, or

prevent access between the Unit and walls,

or another unit.