3 analog in, 4 b.m.s. (pwm) in, 5 shield – AERCO KC1000 Boiler July 2011 User Manual

Page 19: 6 ma out, 7 rs-485 comm, 8 exhaust switch in, 9 interlocks, 1 remote interlock in, Installation

Advertising
background image

INSTALLATION

2-9

2.7.3 ANALOG IN

The ANALOG IN + and – terminals are used

when an external signal is used to drive the

valve position (Direct Drive Mode) or change the

setpoint (Remote Setpoint Mode) of the Boiler.

Either a 4 to 20 mA / 1 to 5 VDC or a 0 to 20 mA

/ 0 to 5 VDC signal may be used to vary the

setpoint or valve position. The factory default

setting is 4 to 20 mA / 1 to 5 VDC, however this

may be changed to 0 to 20 mA / 0 to 5 VDC

using the Configuration Menu described in

Section 3. If voltage rather than current is

selected as the drive signal, a DIP switch must

be set on the PMC Board located inside the

Control Box. Contact the AERCO factory for

information on setting DIP switches.

All supplied signals must be floating

(ungrounded) signals. Connections between the

source and the Boiler’s I/O Box must be made

using twisted shielded pair of 18 –22 AWG wire

such as Belden 9841(see Figure 2.11). Polarity

must be maintained and the shield must be

connected only at the source end and must be

left floating (not connected) at the Boiler’s I/O

Box.

Whether using voltage or current for the drive

signal, they are linearly mapped to a 40°F to

240°F setpoint or a 0% to 100% valve position.

No scaling for these signals is provided.

2.7.4 B.M.S. (PWM) IN

NOTE

Only BMS Model 168 can utilize Pulse

Width Modulation (PWM), not the BMS II

(Model 5R5-384).

These terminals are used to connect the

AERCO Boiler Management System (BMS)

Model 168 to the unit. The BMS Model 168

utilizes a 12 millisecond, ON/OFF duty cycle.

This duty cycle is Pulse Width Modulated (PWM)

to control valve position. A 0% valve position =

a 5% ON pulse and a 100% valve position = a

95% ON pulse.

2.7.5 SHIELD

The SHIELD terminals are used to terminate any

shields used on sensor wires connected to the

unit. Shields must only be connected to these

terminals.

2.7.6 mA OUT

These terminals provide a 4 to 20 mA output

that can be used to monitor setpoint ( 40°F to

220°F), outlet temperature (30°F to 245°F), or

valve position (0% to 100%). This function is

enabled in the Configuration Menu (Section 3,

Table 3-4).

2.7.7 RS-485 COMM

These terminals are used for RS-485 MODBUS

serial communication between the unit and an

external “Master”, such as a Boiler Management

System or other suitable device.

2.7.8 EXHAUST SWITCH IN

These terminals permit an external exhaust

switch to be connected to the exhaust manifold

of the boiler. The exhaust sensor should be a

normally open type switch (such as AERCO Part

No. 123463) that closes (trips) at 500

o

F.

2.7.9 INTERLOCKS

The unit offers two interlock circuits for

interfacing with Energy Management Systems

and auxiliary equipment such as pumps or

louvers. These interlocks are called the Remote

Interlock and Delayed Interlock (Figure 2.11).

The wiring terminals for these interlocks are

located inside the I/O Box on the left side of the

unit. The I/O Box cover contains a wiring

diagram which shows the terminal strip locations

for these interlocks which are labeled REMOTE

INTL’K IN and DELAYED INTL’K IN. Both

interlocks, described in the following

paragraphs, are factory wired in the closed

position.

NOTE:

Both the Delayed Interlock and Remote

Interlock must be in the closed position to

allow the unit to fire.

2.7.9.1 REMOTE INTERLOCK IN

The remote interlock circuit (REMOTE INTL’K

IN) is provided to remotely start (enable) and

stop (disable) the Boiler if desired. The circuit is

24 VAC and comes factory pre-wired closed

(jumpered).

Advertising