MODE OF OPERATION

5-2

11. Press the

CHANGE key. The display will

begin to flash.

12. Use the

and arrow keys to select the

reset ratio determined in step 5.

13. Press

ENTER to save the change.

Refer to paragraph 3.3 for detailed instructions

on menu changing.

5.3 CONSTANT SETPOINT MODE

The Constant Setpoint mode is used when a

fixed header temperature is desired. Common

uses of this mode of operation include water

source heat pump loops, and indirect heat

exchangers for potable hot water systems or

processes.

There are no external sensors necessary to

operate in this mode. While it is necessary to set

the desired setpoint temperature, it is not

necessary to change any other temperature-

related functions. The unit is factory preset with

settings that work well in most applications.

Prior to changing any temperature-related

parameters, other than the setpoint, it is

suggested that an AERCO representative be

contacted. For a complete listing of factory

defaults and descriptions of temperature related

functions, see Appendices A and E.

5.3.1 SETTING THE SETPOINT

The setpoint temperature of the unit is

adjustable from 40°F to 240°F. To set the unit

for operation in the Constant Setpoint Mode, the

following menu settings must be made in the

Configuration Menu:

MENU OPTION

SETTING

Boiler Mode

Constant Setpoint

Internal Setpt

Select desired setpoint

using ▲ and ▼ arrow

keys (40°F to 240°F)

Refer to paragraph 3.3 for detailed instructions

on changing menu options.

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by

an Energy Management System (EMS) or

Building Automation System (BAS). The Remote

Setpoint can be driven by a current or voltage

signal within the following ranges:

4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Remote

Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this

setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by

an EMS or BAS, is used to change the unit's

setpoint. The 4 mA/1V signal is equal to a 40°F

setpoint while a 20 mA /5V signal is equal to a

240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc

signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals

described above, the Remote Setpoint mode

can also driven by a RS485 Modbus Network

signal from an EMS or BAS.
The Remote Setpoint modes of operation can be

used to drive single as well as multiple units.

NOTE:

If a voltage, rather than current signal is used to

control the remote setpoint, a DIP switch

adjustment must be made on the

CPU Board in

the Control Box. Contact your local AERCO

representative for details.

In order to enable the Remote Setpoint Mode,

the following menu setting must be made in the

Configuration Menu:

MENU OPTION

SETTING

Boiler Mode

Remote Setpoint

Remote Signal

4-20mA/1-5V,
0-20mA/0-5V, or
Network

Refer to paragraph 3.3 for detailed instructions

on changing menu options.