Figure 4.1, 1/8” gas plug location, 3 preparing the flue vent probe hole – AERCO KC1000 Boiler July 2011 User Manual

Page 34: Figure 4.2, Analyzer probe hole location, 3 natural gas combustion calibration, Initial start-up, Important

Advertising
background image

INITIAL START-UP

4-2

SSOV

1/8" NPT PLUG

(INSTALL

MANOMETER

HERE)

Figure 4.1

1/8” Gas Plug Location

4.2.3 PREPARING THE FLUE VENT

PROBE HOLE

1. If the unit has been installed using the

recommended AL29-4C vent, there will be a

3/8” hole, 18” to 24” above the exhaust

manifold. The outer vent section, that covers

vent section connections must be loosened

and moved to uncover the hole (see

Fig. 4.2).

2. If equipped with one, adjust the stop on the

combustion analyzer probe so that it

extends into the flue gas flow without hitting

the opposite wall of the flue. Do not insert

the probe at this time.

3/8" - 1/2"

HOLE FOR

COMBUSTION

ANALYZER

PROBE

EXHAUST

MANIFOLD

12" - 18"

Figure 4.2

Analyzer Probe Hole Location

IMPORTANT

The unit is shipped from the factory set up for

either natural gas or propane, as specified by

the Style No. on the Sales Order.
For propane units, refer to paragraph 4.4 for

some additional setup procedures unique to

propane units. The oxygen and carbon

monoxide levels in Tables 1, 2 and 3 apply to

both natural gas and propane. However, it

should be noted that in Table 2 the oxygen and

carbon monoxide levels are measured at 13%

for natural gas and 16% for propane.

4.3 NATURAL GAS COMBUSTION

CALIBRATION

The KC-1000 is shipped combustion calibrated

from the factory. Recalibration as part of a start-

up is necessary due to altitude, gas BTU

content, gas supply piping and supply

regulators. Factory test data sheets are shipped

with each unit as a reference.

The following combustion calibration procedure

closely follows the factory procedure. By

following this procedure, readjustment of the

combustion settings will be kept to a minimum.

1. Open the water supply and return valves to

the unit and ensure that the system pumps

are running.

2. Open the gas supply valve(s) to the unit.

3. If a lockup style regulator is installed as a

gas supply regulator, adjust the gas supply

until a reading of 12” W.C. static pressure is

obtained.

4. Set the

ON/OFF switch to the OFF position.

Turn on AC power to the unit. The display

will show LOSS OF POWER and the time

and date.

5. Set the unit to the Manual Mode by pressing

the

AUTO/MAN switch. A flashing Manual

Valve Position message will be displayed

with the present Air/Fuel Valve position in %

open. Also, the

MANUAL LED will light.

NOTE:

For a review of control panel operating

procedures, refer to Section 3.

6. Adjust the Valve Position to 0% by pressing

the

arrow key.

7. Set the

ON/OFF switch to the ON position.

8. Change the Valve Position to 25% using the

arrow key. This will put the unit into the

starting sequence.