7 combination control system (ccs), 1 combination control system field wiring, 2 combination control system setup and startup – AERCO KC1000 Boiler July 2011 User Manual

Page 43: Mode of operation

Advertising
background image

MODE OF OPERATION

5-5

5.7 COMBINATION CONTROL SYSTEM

(CCS)

NOTE

Only BMS Model 168 can be utilized for

the Combination Mode, not the BMS II

(Model 5R5-384).

A Combination Control System (CCS) is one

that uses multiple boilers to cover both space-

heating and domestic hot water needs. An

AERCO Boiler Management System (BMS)

Model 168 and a Combination Control Panel

(CCP) are necessary to configure this system.

Typically, an adequate number of boilers are

installed to cover the space-heating load on the

design day, however one or more units are used

for the domestic hot water load.
The theory behind this type of system is that the

maximum space-heating load and the maximum

domestic hot water load do not occur simultane-

ously. Therefore, boilers used for the domestic

hot water are capable of switching between

constant setpoint and BMS modes of operation.

These boilers are the combination units and are

referred to as the combo boilers. The combo

boilers heat water to a constant setpoint

temperature. That water is then circulated

through a heat exchanger in a domestic hot

water storage tank.
When the space-heating load is such that all the

space-heating boilers are at 100% valve

position, the BMS will then ask the Combination

Control Panel for the domestic boilers to

become space-heating boilers. Provided the

domestic hot water load is satisfied, the combo

(hot water) boilers will then become space-

heating boilers. If the domestic hot water load is

not satisfied, the combo boiler(s) remain on the

domestic hot water load. If the combo boilers

switch over to space heating, but there is a call

for domestic hot water, the CCP switches the

combo units back to the domestic load.
When the combo units are satisfying the

domestic load they are in constant setpoint

mode of operation. When the combo units

switch over to space heating, their mode of

operation changes to the BMS mode. For more

information concerning the operation of the

Combination Control Panel see the AERCO

CCP-1 literature.

5.7.1 COMBINATION CONTROL SYSTEM

FIELD WIRING

Wiring for this system is between the BMS

Model 168 panel, the CCP and the B.M.S.

(PWM) IN terminals in the I/O Box. Wire the

units using a shielded twisted pair of 18 to 22

AWG wire. When wiring multiple units, each

unit’s wiring must conform to the above. For a

complete CCP system-wiring diagram see the

AERCO CCP-1 literature.

5.7.2 COMBINATION CONTROL SYSTEM

SETUP AND STARTUP

Setup for the Combination Mode requires entries

to be made in the Configuration Menu for boiler

mode, remote signal type and setpoint. The

setpoint is adjustable from 40°F to 240°F.
Enter the following settings in the Configuration

Menu:

MENU OPTION

SETTING

Boiler Mode

Combination

Remote Signal

BMS (PWM Input)

Internal Setpt

40°F to 240°F

Refer to paragraph 3.3 for instructions on

changing menu options.
While it is possible to change other temperature-

related functions for combination mode, these

functions are preset to their factory default

values. These default settings work well in most

applications. It is suggested that AERCO be

contacted prior to changing settings other than

the unit’s setpoint. For a complete listing of

temperature related function defaults, see

Appendix E.
To set the unit to the manual mode, press the

AUTO/MAN switch. The MANUAL LED will

light.
To set the unit back to the auto mode, press the

AUTO/MAN switch. The MANUAL LED will go

off and the

REMOTE LED will light.

When the boiler is switched to BMS mode, the

AERCO BMS controls the valve position. There

are no setup requirements to the boiler(s) in this

mode.

Advertising