Appendix a – AERCO KC1000 Boiler July 2011 User Manual

Page 73

Advertising
background image

APPENDIX A

A-3

APPENDIX A -

BOILER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU (Cont.)

Reset Ratio

Permits setting of Reset Ratio when operating boiler

in the Outdoor Reset Mode. Reset Ratio is

adjustable from 0.1 to 9.9. Default is 1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or

disabled. Default is disabled.

System Start Tmp

If outdoor sensor is enabled, this menu item allows

the system start temperature to be set from 30 to

100°F. Default is 60°F.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to

Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint

(Setpoint Lo Limit to 220°F). Default is 195°F.

Temp Hi Limit

This is the maximum allowable outlet temperature

(40 to 240°F). Any temperature above this setting

will turn off the unit. The temperature must then drop

5° below this setting to allow the unit to run. Default

Hi Limit is 195°F.

Max Valve Positon

Sets the maximum allowable valve position for the

unit (40% to 100%). Default is 100%.

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep

the pump running after the unit turns off. Default is

zero.

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.)

between activating the Aux Relay (due to a demand)

and checking the pre-purge string to start the boiler.

Default is 0 sec.

Failsafe Mode

Allows the Failsafe mode to be set to either

Constant Setpoint or Shutdown. Default is

Shutdown.

Analog Output

Must be set to Valve Pos 0-10V.

Lo Fire Timer

Specifies how long (2 to 600 sec.) to remain in the

low fire position after ignition, before going to the

desired output. Default is 2 sec.

Network Timeout

Specifies the timeout value (seconds) before a

Modbus fault is declared. Available settings range

from 5 to 999 seconds. Default is 30 seconds.

Advertising