4 propane combustion calibration, Figure 4.5, Propane air differential pressure taps – AERCO KC1000 Boiler July 2011 User Manual

Page 37: Initial start-up

Advertising
background image

INITIAL START-UP

4-5

NOTE:

Adjust the inlet air shutter only at 100% valve

position. Do not adjust the differential pressure

regulator.

28. Change the valve position to 30%. Allow

time for the combustion analyzer to settle.

Check the measured oxygen reading to

insure that it is still within the range as per

Table 1.

29. Continue this procedure until all oxygen

levels are within the ranges specified in

Tables 1, 2 and 3.

30. Record all readings on the AERCO start-up

sheet provided with each unit. Proceed to

paragraph 4.5.

4.4 PROPANE COMBUSTION

CALIBRATION

For propane units it will be necessary to install

an additional 8” W.C. This manometer will be

used to measure the pressure drop across the

air/propane mixing orifice. After performing the

setup procedures in paragraphs 4.2.2 through

4.2.4, install the 8” W.C. manometer as

described in steps 1, 2 and 3 which follow.

1. Refer to Fig. 4.5 and remove the 1/8” NPT

plug from the gas inlet pipe ahead of the

burner. Install a 1/8” NPT barbed fitting.

2. Remove the 1/2” NPT plug from the tee

located after the air pressure regulator and

install a 1/2” barbed fitting (see Fig. 4.5).

3. Attach the 8” W.C. manometer to the barbed

fittings installed in steps 1, and 2.

NOTE:

The combustion calibration data in Tables 1, 2

and 3 apply to both natural gas and propane

units. Therefore, refer to these Tables when

performing propane combustion calibration.

Note that Table 2 checks the oxygen and carbon

monoxide levels at a valve position of 16% for

propane instead of the 13% used for natural

gas.

4. While performing the combustion calibration

procedure in paragraph 4.3, measure the

pressure drop across the air/propane mixing

orifice using the 0-8” W.C. manometer.

5. This reading should remain constant at 3.8”

to 4.0” W.C. throughout the operating range.

6. If the pressure drop is not within this range,

remove the cap from the air pressure

regulator.

7. Using a flat blade screwdriver adjust the

regulator until 3.8” to 4.0” W.C. is obtained.

Clockwise will increase the reading and

counterclockwise will decrease the reading.

8. It adjustments are made to this regulator, it

will be necessary to recheck oxygen

readings at 16%, 30%, and 100% valve

positions.

NOTE:

After an adjustment is made to the air regulator,

the cap must be replaced and securely tightened

to obtain an accurate reading

Figure 4.5

Propane Air Differential Pressure Taps

4.5 UNIT REASSEMBLY

Once combustion calibration is set properly, the

unit can be reassembled for permanent

operation as follows:

1. Set the

ON/OFF switch to the OFF position.

Disconnect the AC power supply from the

unit.

2. Shut off the gas supply to the unit.

3. Remove the differential pressure regulator

cap and cap gasket (see Figure 4.3).

4. Apply a drop of silicone adhesive to the

regulator adjusting screw to lock its setting.

5. Reinstall the regulator cap and gasket on

the regulator. Tighten the cap using a

screwdriver or wrench.