Tuning menu, Control panel operating procedures – AERCO KC1000 Boiler July 2011 User Manual

Page 29

Advertising
background image

CONTROL PANEL OPERATING PROCEDURES

3-7

Table 3-4. Configuration Menu - Continued

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

220°F

195°F

Temp Hi Limit

40°F

240°F

195°F

Max Valve Position

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.

Aux Start On Dly

0 sec.

120 sec.

0 sec.

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

*Analog Output

(See

CAUTION at

end of Table 3-4

)

Off, Setpoint, Outlet Temp,

Valve Position 4-20 mA,

Valve Position 0-10V

*Valve

Position

0-10V

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

5°F

Network Timeout

5 Sec

999 Sec

30 Sec

HI DB Setpt EN

0%

100%

30%

Demand Offsert

0

25

10

Deadband High

0

25

2

Deadband Low

0

25

2

*CAUTION:

DO NOT CHANGE the Analog Output Menu Item from its Default setting

(Valve Position 0-10V).

3.7. TUNING MENU

The Tuning Menu items in Table 3-5 are Factory

set for each individual unit.


Do not change these menu entries unless

specifically requested to do so by Factory-

Trained personnel.

Table 3-5. Tuning Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Prop Band

1°F

120°F

70°F

Integral Gain

0.00

2.00

1.00

Derivative Time

0.0 min

2.0 min

0.0 min

Reset Defaults?

Yes

No

Are You Sure?

No