2 installing the supply gas manometer, Initial start-up – AERCO KC1000 Boiler July 2011 User Manual

Page 33

Advertising
background image

INITIAL START-UP

4-1

SECTION 4 - INITIAL START- UP

4.1 INITIAL START- UP REQUIREMENTS

The initial start-up of the KC-1000 Boiler is

comprised of the following steps:

installation completed 100%

combustion calibration

proper setting of controls and limits

mode of operation settings (see Section 5)

safety device testing (see Section 6)

Installation procedures should be completed

100% before performing initial start-up and initial

the start-up must be complete prior to putting the

unit into service. Starting a unit without the

proper piping, venting, or electrical systems can

be dangerous and void the product’s warranty.

These start-up instructions should be precisely

followed in order for the unit to operate safely, at

a high thermal efficiency, and with low flue gas

emissions.

Initial unit start-up is to be performed ONLY by

AERCO factory trained start-up and service

personnel. After following the steps in this

section, it will be necessary to perform the mode

of operation settings in section 5, and the safety

control test procedures in section 6 to complete

the initial unit start-up.

An AERCO Gas Fired Startup Sheet included

with each KC-1000 must be completed for each

unit for warranty validation and a copy must be

returned promptly to AERCO at:

AERCO International, Inc.

159 Paris Ave.

Northvale, NJ 07647

WARNING

!

DO NOT ATTEMPT TO FIRE THE UNIT

WITHOUT FULL WATER LEVEL. THIS

CAN SERIOUSLY DAMAGE THE UNIT

AND MAY RESULT IN PERSONAL

INJURY OR PROPERTY DAMAGE. THIS

IS NOT COVERED BY WARRANTY.

CAUTION!

All installation procedures in Section 2 must

be completed before attempting to start the

unit.

4.2 TOOLS AND INSTRUMENTATION

FOR COMBUSTION CALIBRATION

To properly perform combustion calibration, the

proper instruments and tools must be used and

correctly installed on the unit. The following

paragraphs outline the necessary tools and

instrumentation as well as their installation.

4.2.1 REQUIRED TOOLS AND

INSTRUMENTATION

The following tools and instrumentation are

necessary to perform combustion calibration of

the unit:

1. A digital combustion analyzer with oxygen

accuracy to 0.4%, and carbon monoxide in

PPM.

2. *A 16" W.C. manometer and plastic tubing.

3. One 1/4” and two 1/8” NPT-to-barbed fittings

for use with manometers.

4. A flat-tip screwdriver for adjusting the

AERCO differential gas pressure regulator.

5. Small and large flat blade screwdrivers.

6. 7/16" open end wrench and small adjustable

wrenches.

7. Tube of silicone adhesive

*For propane fired units: an additional 8" W.C.

manometer and 1/2" NPT to barbed fitting is

needed.

4.2.2 INSTALLING THE SUPPLY GAS

MANOMETER

1. Close the main manual gas supply valve up

stream of the unit.

2. Remove the 1/4" NPT pipe plug from the

port on the inlet side of the safety shut off

valve (see Figure 4.1).

3. Install a barbed fitting into the pipe plug

tapping.

4. Attach one end of a length of plastic tubing

to the barbed fitting and one end to the 16"

W.C. manometer.

Advertising