SAFETY DEVICE TESTING

6-5

SSOV

ACTUATOR

COVER

SSOV

COVER

SCREW

Figure 6.6

SSOV Actuator Cover Screw Location

6.10 PURGE SWITCH OPEN DURING

PURGE

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and

set the valve position between 25% and

30%.

2. Remove the air/fuel valve cover by rotating

the cover counterclockwise to unlock it and

then pulling it towards you. See Figure 6.7.

3. Remove one of the two wires from the purge

switch (Figuire 6.8) and start the unit.

4. The unit should begin to start, then shut

down and display PRG SWITCH OPEN

DURING PURGE.

5. Replace the wire on the purge switch and

depress the

CLEAR button. The unit should

restart.

VALVE

COVER

Figure 6.7

Air/Fuel Valve Cover Location

IGNITION

POSITION

SWITCH

PURGE

POSITION

SWITCH

169

170

172

171

STEPPER

MOTOR

DIAL

BLOWER

BURNER

Figure 6.9

Air/Fuel Valve Purge and Ignition Switch

Locations