1 remote setpoint field wiring, 2 remote setpoint startup, 5 direct drive modes – AERCO KC1000 Boiler July 2011 User Manual

Page 41: Mode of operation

Advertising
background image

MODE OF OPERATION

5-3

If the Network setting is selected for RS485

Modbus operation, a valid Comm Address must

be entered in the Setup Menu. Refer to Modbus

Communication Manual GF-114 for additional

information.
While it is possible to change the settings of

temperature related functions, the unit is factory

preset with settings that work well in most

applications. It is suggested that an AERCO

representative be contacted, prior to changing

any temperature related function settings. For

descriptions of temperature-related functions

and their factory defaults, refer to Appendices A

and E.

5.4.1 REMOTE SETPOINT FIELD WIRING

The only wiring connections necessary for the

Remote Setpoint mode are connection of the

remote signal leads from the source to the unit’s

I/O Box. The I/O Box is located on the front

panel of the Benchmark Boiler. For either a 4-

20mA/0-5V or a 0-20mA/0-5V setting, the

connections are made at the ANALOG IN

terminals in the I/O Box. For a Network setting,

the connections are made at the RS-485 COMM

terminals in the I/O Box. The signal must be

floating, (ungrounded) at the I/O Box and the

wire used must be a two wire shielded pair from

18 to 22 AWG. Polarity must be observed. The

source end of the shield must be connected at

the source. When driving multiple units, each

unit’s wiring must conform to the above.

5.4.2 REMOTE SETPOINT STARTUP

Since this mode of operation is factory preset

and the setpoint is being externally controlled,

no startup instructions are necessary. In this

mode, the

REMOTE LED will light when the

external signal is present.
To operate the unit in the Manual mode, press

the

AUTO/MAN switch. The REMOTE LED will

go off and the

MANUAL LED will light.

To change back to the Remote Setpoint mode,

simply press the

AUTO/MAN switch. The

REMOTE LED will again light and the MANUAL

LED will go off.

5.5 DIRECT DRIVE MODES

The unit’s air/fuel valve position can be changed

by a remote signal which is typically sent from

an Energy Management System (EMS) or from

a Building Automation System (BAS). The Direct

Drive mode can be driven by a current or

voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive

mode is 4-20 mA/1-5 Vdc. With this setting, a 4

to 20 mA signal, sent by an EMS or BAS is used

to change the unit’s valve position from 0% to

100%. A 4 mA/1V signal is equal to a 0% valve

position, while a 20 mA /5V signal is equal to a

100% valve position. When a 0-20 mA/0-5 Vdc

signal is used, zero is equal to a 0% valve

position.
In addition to the current and voltage signals

described above, the Direct Drive mode can also

driven by a RS485 Modbus Network signal from

an EMS or BAS.
When in a Direct Drive mode, the unit is a slave

to the EMS or BAS and does not have a role in

temperature control. Direct Drive can be used to

drive single, or multiple units.

NOTE:

If a voltage, rather than current signal is used to

control the valve position, a DIP switch

adjustment must be made on the

PMC Board in

the Control Box. Contact your local AERCO

representative for details.

To enable the Direct Drive Mode, the following

menu setting must be made in the Configuration

Menu:

MENU OPTION

SETTING

Boiler Mode

Direct Drive

Remote Signal

4-20mA/1-5V,
0-20mA/0-5V, or
Network

Refer to paragraph 3.3 for instructions on

changing menu options.

Advertising