MAINTENANCE

7-3

5. Remove the flame detector and ignition

cable wires from the flame detector and

ignitor contactor. Remove the ignitor and

flame detector per paragraphs 7.2, and 7.3.

6. Remove the grounding terminal from the

burner by loosening the upper screw and

sliding the connector from the grounding

rod. (See Figure 7.2).

Figure 7.2

Grounding Terminal Location

7. Using a 7/16” socket or open end wrench

remove the four 1/4”-20 nuts on the gas inlet

pipe flange at the burner (See Figure 7.3).

8. Using two 9/16” wrenches remove the 3/8"-

16 hex nuts and bolts on the gas inlet pipe

flange at the air/fuel valve (See Figure 7.3).

9. Loosen the hose clamp nearest the air/fuel

valve outlet on the air/fuel valve to burner

adapter (See Figure 7.3).

10. Using a 1/2” socket wrench remove six

5/16-18 hex nuts supporting the burner (See

Fig. 7.3).

Figure 7.3

Burner Disassembly Diagram

11. Lower the burner while sliding the air hose

off the air/fuel valve. Remove the burner

through the rear of the unit.

12. Disconnect the exhaust temperature sensor

by unscrewing it from the exhaust manifold

(See Fig. 7.4).

Figure 7.4

Exhaust Sensor Connector Location

13. Disconnect the air/fuel valve wire harness,

the 12 pin connector, from the control panel.

14. Disconnect wires #24 and #17 from the

blower proof switch (See Figure 7.5).

TO FRAME

HARNESS

BLOWER PROOF

SWITCH

AIR/FUEL VALVE

Figure 7.5

Blower Proof Switch Wire Locations

15. Loosen the hose clamp on the air/fuel valve

inlet and slide the clamp back towards the

blower (See Figure 7.6).